User Manual Troubleshooting
- 185 -
Fault
Code
Name Possible Causes Solution Level
Err36
RUN contactor
feedback
abnormal
101: The feedback of the
RUN contactor is active, but
the contactor has no output.
102: The controller outputs
the RUN signal but receives
no RUN feedback.
103: The startup current of
the asynchronous motor is
too small.
104: When both feedback
signals of the RUN
contactor are enabled, their
states are inconsistent.
101, 102, 104:
Check whether the feedback
contact of the contactor acts
properly.
Check the signal feature (NO,
NC) of the feedback contact.
103:
Check whether the output
cables UVW of the controller
are connected properly.
Check whether the control
circuit of the RUN contactor
coil is normal.
5A
Err37
Brake
contactor
feedback
abnormal
101: The output of the brake
contactor is inconsistent
with the feedback.
102: When both feedback
signals of the brake
contactor are enabled, their
states are inconsistent.
103: The output of the brake
contactor is inconsistent
with the feedback 2.
104: When both feedback
2 signals of the brake
contactor are enabled, their
states are inconsistent.
101 to 104:
Check whether the brake coil
and feedback contact are
correct.
Check the signal feature (NO,
NC) of the feedback contact.
Check whether the control
circuit of the brake contactor
coil is normal.
5A
Err38
Encoder signal
abnormal
101: Pulse signal change
in F4-03 does not change
within the time threshold in
of F1-13.
102: The running direction
and pulse direction are
inconsistent.
101, 102:
Check whether the encoder is
used correctly.
Exchange phases A and B of
the encoder.
Check whether the system and
signal cables are grounded
reliably.
Check whether cabling
between the encoder and the
PG card is correct.
5A
Err39 Motor overheat
101: The motor overheat
relay input remains valid for
a certain time.
101:
Check whether the thermal
protection relay is normal.
Check whether the motor is
used properly and whether it is
damaged.
Improve cooling conditions of
the motor.
3A