F1: Program Mode
4-17
4
Motion 4000
HONEYWELL FIRE OPERATION?
Only if FIRE SVCE. CODE option set to AUSTRALIA (See “FIRE SVCE. CODE” on
page 4-16). If set to YES, Australia fire code will conform to Honeywell requirements.
If set to NO, controller will conform to standard Australia code.
NYC FIRE PHASE 2 AND ANSI 89?
Available only if FIRE SVCE. CODE is set to ANSI A17.1 89 (See “FIRE SVCE. CODE”
on page 4-16). If set to YES, ANSI A17.1 89 Fire Code will conform to New York City
Fire Code requirements when on Fire Phase 2. If set to NO, controller will conform to
standard ANSI A17.1 89 Fire Code.
WHITE PLAINS, NY FIRE CODE?
Available only if FIRE SVCE. CODE set to ANSI17.1 89 (See “FIRE SVCE. CODE” on
page 4-16). The city of White Plains requires that, if fire phase one is still in effect, the
car can exit fire phase two regardless of the position of the doors. Set to YES to comply
with this requirement.
MASS 524 CMR FIRE CODE?
Available only if “FIRE SVCE. CODE” set to “A17.1 - 2000". If set to YES, ASME A17.1-
2000 fire code will conform to Massachusetts 524 CMR requirements. If set to NO,
controller will conform to standard ASME A17.1-2000 code.
ASME A17.1A 2000 ADDENDA
Set to the appropriate addenda for your jurisdiction. (2005, 2007, NONE)
DISABLE DPM ON FIRE PH.2?
If Yes, Door Position Monitoring is disabled when the car is on In Car Firefighter oper-
ation (Fire Phase 2). If No, DPM is not disabled on Fire Phase 2.
•LOW VOLTAGE FIRE SENSORS?
If the fire sensors on this job use 24V signal levels, set this option to Yes.
If set to No, the signal level is assumed to be 120 VAC.
LATCH FLASHING FIRE HAT?
If a fire/smoke sensor in the elevator machine room or hoistway
1
initiates an alarm, the fire hat
indicator will flash. A flashing indicator may be reset in one of two ways:
If this option is set to Yes: Fire service must be reset using the fire service key switch
before the indicator will cease flashing. Resetting an individual initiating alarm will
not stop the indicator from flashing.
If this option is set to No: The indicator will stop flashing once the initiating alarm is
reset.
1. A17.1/B44 code edition/addenda or jurisdiction dependent: (A) for ASME A17.1-2004/CSA B44-04 and later,
the machine room or hoistway sensor must be the sensor that initiated Fire Phase I for the hat to flash; or (B) for
earlier editions of A17.1/B44, the fire hat will flash any time the machine room or hoistway sensor is active,
regardless of which device initiated Fire Phase I. Also, some jurisdictions occasionally modify the A17.1/B44
requirements, so please consult with the jurisdictional authorities for additional requirements.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motion Control Engineering Motion 4000 and is the answer not in the manual?

Motion Control Engineering Motion 4000 Specifications

General IconGeneral
BrandMotion Control Engineering
ModelMotion 4000
CategoryController
LanguageEnglish

Related product manuals