Installation
2-4 Manual # 42-02-2P24
Electrical Noise
Electrical noise readily occurs when two wires run along side one another with one of them a
high power conductor and the other a low signal level conductor. The easiest way to avoid noise
problems is to keep low-level wiring in separate conduit from high power wiring. If high and
low power wiring must be run in the same duct, separate them by a minimum of three to four
inches. If one must cross the other, it should be at a ninety degree angle.
Alternately, low level wiring may use shielded cable. The shield drains induced voltage to
ground. The shield must be connected to ground at one end only.
EMI/RFI
To avoid EMI/RFI interference:
• Keep motor leads as short as possible. Run them in a separate conduit.
• Run main line supply leads to the controller or isolation transformer in a separate conduit.
• Run leads from the isolation transformer to the drive cabinet in a separate conduit.
• The controller door will protect against interference only when closed.
Recommended Tools and Test Equipment
Recommended tools and test equipment:
• Digital multimeter, Fluke series 75, 76, 77 or equivalent
• Hand-held tachometer
• Clamp-on AC ammeter
• Hand-held radios
•Test weights

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motion Control Engineering Motion 4000 and is the answer not in the manual?

Motion Control Engineering Motion 4000 Specifications

General IconGeneral
BrandMotion Control Engineering
ModelMotion 4000
CategoryController
LanguageEnglish

Related product manuals