User Interface
4-24 Manual # 42-02-2P24
DOOR HOLD INPUT TIMER (Range: 0-240 Seconds)
Timer used only if there is a DHLD (Door Hold) input to the controller (See “Spare
Inputs Menu” on page 4-26). A Door Hold Open button is usually connected to this
input. Timer determines how long the doors will stay open when the door hold open
button is pressed. The timer is canceled and the doors will begin to close if either the
Door Close button or a Car Call button is pressed. If a Door Hold Key switch (instead of
a button) is connected to the DHLD input, timer value should be set to zero so that the
doors will close immediately when the switch is turned OFF.
PARKING DELAY TIMER (Range: 0.0-6.0 Minutes)
Used only if a parking floor is selected. Timer starts when car is free of call demand.
The car will park after the timer expires.
FAN/LIGHT OUTPUT TIMER (Range: 5.0-20.0 Minutes)
Used with the FLO output, this timer sets the amount of time that will pass before the
FLO output is activated to shut off the car light and fan. Time will start when the car
becomes inactive. The FLO output is typically connected to a relay that turns OFF the
fan and light in the car. This is also used for PI Turned Off if No Demand.
HOSPITAL EMERGENCY TIMER (Range: 1.0-10.0 Minutes)
Sets the amount of time the car will remain at the hospital emergency floor with the
doors open before automatically returning to normal service. (See “HOSPITAL
EMERG. OPERATION?” on page 4-45.)
DOOR OPEN PROTECTION TIMER (Range 8 - 30 Seconds)
Determines how long the door operator will attempt to open the doors. If DOL does
not go low within this time, the doors will begin to close.
PASSWORD TIMER (Range: 0 - 30 Seconds)
Determines length of time the car will wait for correct password entry through car call
COP buttons after a secured car call has been requested before cancelling the call entry
cycle. (Applies only to BSI security.)
CTL DOOR OPEN TIMER (Range: 2.0 - 60.0 seconds)
Used to specify how long the doors should remain open after car returns to lobby when
the CTL (Car to Lobby) input is activated.
DOOR BUZZER TIMER (Range: 0 - 30 Seconds)
Determines length of time door buzzer sounds before doors are automatically closed.
OPN/CLS INTRLOCK TIMER (Range: 050ms - 950ms, 50ms increments)
Introduces a delay when closing or opening doors are abruptly reversed (i.e., photo eye
activation, door button press, etc.). This may be required if the door operator is sensi-
tive to such reversal due to de-bounce capability.
Set to NONE if unnecessary.
FIRE PH1 RECLOSE TIMER (Range: Disabled or 1 - 120 seconds)
If set to a value other than NONE, the doors will close after the set number of seconds
following a Fire Service Phase 1 recall. Doors may be opened using in-car or hall door
open buttons.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motion Control Engineering Motion 4000 and is the answer not in the manual?

Motion Control Engineering Motion 4000 Specifications

General IconGeneral
BrandMotion Control Engineering
ModelMotion 4000
CategoryController
LanguageEnglish

Related product manuals