User Interface
4-44 Manual # 42-02-2P24
• AUTOMATIC FLOOR STOP OPTION? / AUTOMATIC STOP FLOOR #?
• If you want to use this option, set to a specific floor number. The car will automatically
stop at that floor on any run that would normally pass the floor.
• CC CANCEL W/DIR REVERSAL?
• Causes all previously registered car calls to be canceled when the car reverses travel
direction.
• CANCEL CAR CALLS BEHIND CAR?
• If set to YES and the car has a direction arrow (SUA/SDA), no car calls can be regis-
tered behind the current car position. For example: If a car is at the fifth floor moving
down, no car calls can be registered for the sixth floor and above.
• CE ELECTRONICS BOARD?
• Informs the controller of the revision level, 1 or 2, of the CE interface board in use.
• MASSACHUSETTS EMS SERVICE? / EMS SERVICE FLOOR #
• Provided in the state of Massachusetts only, this option is key-operated and provides
immediate car service for Massachusetts Emergency Medical Service personnel.
• BSI SECURITY KEY
• Standard Security is initiated by the BSI Security Key. There are three possible set-
tings: ACTIVATED, ENABLED, or DEACTIVATED.
• If set to ACTIVATED, Security is initiated.
• If set to ENABLED, Security is initiated only if the Building Security Input (BSI) is
turned On.
• If set to DEACTIVATED, Security is deactivated regardless of the status of the BSI
input.
• PI TURNED OFF IF NO DEMAND?
• When set to YES, allows PI outputs to turn OFF if the car has been inactive for a
selected time (from 1 to 10 minutes) as determined by the fan/light timer. Please refer
to “FAN/LIGHT OUTPUT TIMER (Range: 5.0-20.0 Minutes)” on page 4-24.