5-95
5-8 Restart Functions
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
   5
Functions
The major parameters relating to frequency matching restart and frequency pull-in restart are
listed below. 
For details, refer to the section on each function. 
Classification
Parameter 
No.
Function name Data
Default 
setting
Unit
Common b003
Restart Standby 
Time
0.3 to 100.0
Time until restart
1.0 s
Frequency 
matching 
restart
b007
Frequency 
Matching Lower 
Limit Frequency 
Setting
0.00 to 400.0 (1000.)
If the frequency drops to b007 
or below during the motor free 
run, the Inverter restarts at 0 
Hz. 
0.00 Hz
Frequency 
pull-in restart
b028
Frequency Pull-in 
Restart Level
0.20 × Rated current to 2.00 × 
Rated current
Inverter 
rated 
current
A
b029
Frequency Pull-in 
Restart Parameter
0.10 to 30.00
Frequency reduction time
0.50 s
b030
Starting 
Frequency at 
Frequency Pull-in 
Restart Selection
00: Frequency at interruption
00 −01: Maximun frequency
02: Set frequency
FW input
(forward)
Power supply
Output current
Inverter output
frequency
Motor rotation speed
Decelerates according to b029. 
Frequency selected in b030
b028
b003