5-97
5-8 Restart Functions
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
   5
Functions
b007
Frequency 
Matching Lower 
Limit Frequency 
Setting
0.00 to 
400.0 
(1000.)
If the frequency drops to b007 or 
below while the motor is running 
freely, the Inverter restarts at 0 
Hz. (examples 3, 4)
0.00 Hz
b008
Overvoltage/
Overcurrent 
Restart Selection
00 Trip
00 −
01 0 Hz restart
02 Frequency matching restart
03
Trip after frequency matching 
deceleration stop
04 Frequency pull-in restart
b010
Overvoltage/
Overcurrent 
Restart Count 
Selection
1 to 3
Number of retries for restart upon 
overvoltage/overcurrent
*5
3Time
b011
Overvoltage/
Overcurrent 
Restart Standby 
Time
0.3 to 100. Wait time until restart 1.0 s
b028
Frequency Pull-in 
Restart Level
0.20 × Rated 
current to 
2.00 × Rated 
current
Current limit level at frequency 
pull-in restart
Inverter
rated 
current
A
b029
Frequency Pull-in 
Restart Parameter
0.1 to 3000.
Frequency reduction time at 
frequency pull-in restart
0.50 s
b030
Starting 
Frequency at 
Frequency Pull-in 
Restart Selection
00 Frequency at interruption
00 −01 Maximum frequency
02 Set frequency
C021 to 
C022, C026
Multi-function 
Output Terminal 
Selection
Multi-function 
Relay Output 
Function Selection
09 UV: Signal during undervoltage −−
*1.Even when Retry Selection (b001) is set to any restart function (01 to 03) and Momentary Power
Interruption/Undervoltage Trip during Stop Selection (b004) is disabled (00 or 02), a trip still occurs if
the momentary power interruption time exceeds the allowable momentary power interruption/
undervoltage time. (Example 2)
*2.Even if a restart function is selected, the Inverter trips when undervoltage remains for 40 seconds or
longer.
*3.0 Hz restart may occur in the following cases: 
• The output frequency is one-half the base frequency or below
• The induced voltage of the motor attenuates quickly
*4.If an overvoltage/overcurrent trip occurs during declaration, Undervoltage Error E09 is displayed and
the motor goes into free-run status. In this case, increase the deceleration time.
*5.Even when a restart operation upon trip is selected, the Inverter continues to trip if the cause of the trip
is not yet removed after Restart Standby Time (b003) elapses. In this case, increase the restart standby
time.
Parameter 
No.
Function name Data Description
Default 
setting
Unit