6-29
6-8 List of Modbus Communication (Modbus-RTU) Data
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
6
Communication Function
0032h FBV (FB status output) R
1: ON
0: OFF
0033h
NDc (communication
disconnection detection)
R
1: ON
0: OFF
0034h LOG1 (logic operation output 1) R
1: ON
0: OFF
0035h LOG2 (logic operation output 2) R
1: ON
0: OFF
0036h LOG3 (logic operation output 3) R
1: ON
0: OFF
0037h
Reserved −−0038h
0039h
003Ah WAC (capacitor life warning) R
1: ON
0: OFF
003Bh WAF (cooling fan life warning) R
1: ON
0: OFF
003Ch FR (starting contact signal) R
1: ON
0: OFF
003Dh OHF (fin overheat warning) R
1: ON
0: OFF
003Eh LOC (low current signal) R
1: ON
0: OFF
003Fh
Reserved −−
0040h
0041h
0042h
0043h
0044h
0045h IRDY (operation ready) R
1: ON
0: OFF
0046h FWR (during forward operation) R
1: ON
0: OFF
0047h RVR (during reverse operation) R
1: ON
0: OFF
0048h MJA (fatal fault signal) R
1: ON
0: OFF
0049h Data being written R
1: Being written
0: Normal
004Ah CRC error R
1: Error
0: No error
*2
004Bh Overrun error R
1: Error
0: No error
*2
004Ch Framing error R
1: Error
0: No error
*2
004Dh Parity error R
1: Error
0: No error
*2
Coil No. Function name R/W Description

Table of Contents

Related product manuals