6-8 List of Modbus Communication (Modbus-RTU) Data
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
6
Communication Function
0030h Fault Monitor 4: Cause
d084 R
Refer to "Inverter Fault Factor
List" on page 6-35.
−
0031h
Fault Monitor 4:
Inverter Status
Refer to "Inverter Fault Factor
List" on page 6-35.
−
0032h
Fault Monitor 4:
Frequency (HIGH)
0 to 100000 0.01 [Hz]
0033h
Fault Monitor 4:
Frequency (LOW)
0034h
Fault Monitor 4:
Current
d084 R
Output current value at the
time of tripping
0.01 [A]
0035h
Fault Monitor 4:
Voltage
DC input voltage at the time of
tripping
0.1 [V]
0036h
Fault Monitor 4: RUN
Time (HIGH)
Total RUN time at the time of
tripping
1 [h]
0037h
Fault Monitor 4: RUN
Time (LOW)
0038h
Fault Monitor 4: ON
Time (HIGH)
Power ON time at the time of
tripping
1 [h]
0039h
Fault Monitor 4: ON
Time (LOW)
003Ah Fault Monitor 5: Cause
d085 R
Refer to "Inverter Fault Factor
List" on page 6-35.
−
003Bh
Fault Monitor 5:
Inverter Status
Refer to "Inverter Fault Factor
List" on page 6-35.
−
003Ch
Fault Monitor 5:
Frequency (HIGH)
0 to 100000 0.01 [Hz]
003Dh
Fault Monitor 5:
Frequency (LOW)
003Eh
Fault Monitor 5:
Current
Output current value at the
time of tripping
0.01 [A]
003Fh
Fault Monitor 5:
Voltage
DC input voltage at the time of
tripping
0.1 [V]
0040h
Fault Monitor 5: RUN
Time (HIGH)
Total RUN time at the time of
tripping
1 [h]
0041h
Fault Monitor 5: RUN
Time (LOW)
0042h
Fault Monitor 5: ON
Time (HIGH)
Power ON time at the time of
tripping
1 [h]
0043h
Fault Monitor 5: ON
Time (LOW)
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting
parameters
Data
resolution