9-2
9-1 Standard Specification List
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
9
Specifications
Three-phase 400 V Class
CT: Heavy load, VT: Light load
Function name 3-phase 400 V
Model name
(3G3MX2-)
A4004 A4007 A4015 A4022 A4030 A4040 A4055 A4075 A4110 A4150
Applicable
motor
capacity
kW
CT
0.4 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11 15
VT
0.75 1.5 2.2 3.0 4.0 5.5 7.5 11 15 18.5
HP
CT
1/2 1 2 3 4 5 7 1/2 10 15 20
VT
1 2 3 4 57 1/210152025
Rated
output
capacity
[kVA]
380 V
CT
1.1 2.2 3.1 3.6 4.7 6.0 9.7 11.8 15.7 20.4
VT
1.3 2.6 3.5 4.5 5.7 7.3 11.5 15.1 20.4 25.0
480 V
CT
1.4 2.8 3.9 4.5 5.9 7.6 12.3 14.9 19.9 25.7
VT
1.7 3.4 4.4 5.7 7.3 9.2 14.5 19.1 25.7 31.5
Rated input voltage 3-phase 380 V − 15% to 480 V + 10%, 50/60 ± 5%
Rated output
voltage
3-phase 380 to 480 V (The output cannot exceed the incoming voltage).
Rated output
current [A]
CT
1.8 3.4 4.8 5.5 7.2 9.2 14.8 18.0 24.0 31.0
VT
2.1 4.1 5.4 6.9 8.8 11.1 17.5 23.0 31.0 38.0
Short-time
deceleration braking
torque (%)
(Discharge Resistor
not connected)
50 50 50 20 20 20 20 20 10 10
Braking
Resistor
circuit
*1
Regenerative
braking
Built-in Braking Resistor circuit (separate Discharge Resistor)
Min.
connectable
resistance
[
Ω
]
180 180 180 100 100 100 70 70 70 35
Weight [kg] 1.5 1.6 1.8 1.9 1.9 2.1 3.5 3.5 4.7 5.2
Dimensions (width
× height) [mm]
108 × 128
140 ×
128
140 × 260 180 × 296
Dimensions (depth)
[mm]
143.5
170.5 170.5 155 175
*1. The BRD usage is 10%.