4-5
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
   4
Parameter List
Parameter 
No.
Function name Monitor or data range
Default 
setting
Set data
Data can 
be set 
during 
RUN
Data can be 
changed 
during RUN
Unit
Page
Basic setting 
A001
Frequency 
Reference 
Selection 1
00: Digital Operator (volume)
01: Control circuit terminal 
block
02: Digital Operator (F001)
03: Modbus communication 
(Modbus-RTU)
04: Do not set.
06: Pulse train frequency
07: Do not set.
10: Operation function output
02 no no
− 5-15
A201
Frequency 
Reference 
Selection 2
02 no no
A002
RUN Command 
Selection 1
01: Control circuit terminal 
block
02: Digital Operator
03: Modbus communication 
(Modbus-RTU)
04: Do not set.
02 no no
− 5-22
A202
RUN Command 
Selection 2
02 no no
A003
Base 
Frequency 1
30.0. to Maximum Frequency 1 
[A004]
60.0 no no Hz
5-26
A203
Base 
Frequency 2
30.0 to Maximum Frequency 2 
[A204]
60.0 no no Hz
A004
Maximum 
Frequency 1
30.0 to 400.0 (1000.) 60.0 no no Hz
5-28
A204
Maximum 
Frequency 2
30.0 to 400.0 (1000.) 60.0 no no Hz
Analog input, others
A005 FV/FI Selection
00: Switch between FV 
(voltage)/FI (current)
02: Switch between FV 
(voltage)/volume
*1
03: Switch between FI 
(current)/volume
*1
00 no no − 5-38
A011
FV Start 
Frequency
0.00 to 99.99
100.0 to 400.0 (1000.)
0.00 no yes Hz
5-40
A012
FV End 
Frequency
0.00 to 99.99
100.0 to 400.0 (1000.)
0.00 no yes Hz
A013 FV Start Ratio 0. to FV end ratio 0. no yes %
A014 FV End Ratio FV start ratio to 100. 100. no yes %
A015
FV Start 
Selection
00: Start Frequency A011
01: 0 Hz
01 no yes −
A016
Analog Input 
Filter
(FV, FI 
Sampling)
1. to 30.
31. (with 500 ms filter ±0.1 Hz 
hysteresis)
8noyes− 5-38
A017 (Reserved) Do not change. 00 −−−−
*1. Enabled when the Digital Operator with Volume 3G3AX-OP01 is connected.