4-19
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
4
Parameter List
Others
b036
Reduced
Voltage Startup
Selection
0 (Reduced voltage startup
time: short) to 255 (Reduced
voltage startup time: long)
2noyes 5-58
b037
Display
Selection
00: Complete display
01: Individual display of
functions
02: User setting + b037
03: Data comparison display
04: Basic display
05: Monitor display only
04 no yes 5-88
b038
Initial Screen
Selection
000: Screen on which the
Enter key was last
pressed
001 to 060: d001 to d060
201: F001
202: Do not set.
001 no yes 5-86
b039
User Parameter
Automatic
Setting
Function
00: Disabled
01: Enabled
00 no yes 5-174
Torque limit
b040
Torque Limit
Selection
00: Four-quadrant separate
setting
01: Terminal switching
02: Analog voltage input
00 no yes
5-153
b041
Torque Limit 1
(Four-quadrant
Mode Forward
Power
Running)
0. to 200.
no (Torque limit disabled)
200. no yes
%
b042
Torque Limit 2
(Four-quadrant
Mode Reverse
Regeneration)
200. no yes
b043
Torque Limit 3
(Four-quadrant
Mode Reverse
Power
Running)
200. no yes
b044
Torque Limit 4
(Four-quadrant
Mode Forward
Regeneration)
200. no yes
b045
Torque
LADSTOP
Selection
00: Disabled
01: Enabled
00 no yes 5-154
b046
Reverse
Rotation
Prevention
Selection
00: Disabled
01: Enabled
00 no yes 5-156
Other
b049
Heavy Load/
Light Load
Selection
00: Heavy load mode
01: Light load mode
00 no no 5-13
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page

Table of Contents