Install the Disk Backplane
2.
Using a Torx T10 screwdriver, tighten the three storage drive backplane captive
screws clockwise until the disk backplane is secure [2].
3.
Reconnect the disk backplane power cable to the disk backplane [3].
4.
Reconnect the disk backplane data cable and temperature sensor cable to the
disk backplane [4].
5.
Reconnect the SAS cables or the NVMe cables (if present) to the disk backplane
[5].
6.
Reinstall the super capacitor by pressing down on the capacitor to secure it to
the reclosable fastener in the chassis.
7.
Reinstall all of the storage drives into the server.
See “Install a Storage Drive” on page 70.
8.
Return the server to operation.
a.
Install the server top cover.
See “Install the Server Top Cover” on page 210
b.
Return the server to the normal rack position.
See “Return the Server to the Normal Rack Position” on page 212.
c.
Reconnect the data cables to the server and reconnect the power cords to
the server power supplies.
See “Reconnect Data Cables and Power Cords” on page 214.
d.
Power on the server.
See “Power On the Server” on page 214.
Verify that the System OK status indicator is steady on.
Related Information
■
“Remove the Disk Backplane” on page 151