Analog Modules
4-35
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
4.6 Conversion, Cycle, Setting and Response Time of Analog
Modules
Conversion time of analog input channels
The conversion time consists of a basic conversion time and additional processing
times of the module for:
Resistance test
Wire-break monitoring
The basic conversion time depends directly on the conversion method of the
analog input channel (integrating method, instantaneous value conversion).
In the case of integrating conversion methods, the integration time has a direct
influence on the conversion time. The integration time depends on the interference
frequency suppression that you set in STEP 7 (refer to Section 4.7.1).
For the basic conversion times and additional processing times of the different
analog modules refer to the technical specifications of the module concerned,
starting at Section 4.18.
Scan time of analog input channels
Analog-to-digital conversion and the transfer of the digitized measured values to
the memory and/or to the bus backplane are performed sequentially – in other
words, the analog input channels are converted one after the other. The scan time
– in other words, the time elapsing until an analog input value is again converted, is
the sum of the conversion times of all activated analog input channels of the
analog input module.
The following figure illustrates the components of the scan time for an n-channel
analog module.
Conversion time,
channel 1
Conversion time,
channel 2
Conversion time,
channel n
Scan time
Figure 4-4 Scan time of an analog input or output module

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals