EasyManuals Logo

Siemens SIMATIC S7-300 Module data Reference Manual

Siemens SIMATIC S7-300 Module data
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #242 background imageLoading...
Page #242 background image
Analog Modules
4-36
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Conversion and scan times for analog input channels in channel groups
When the analog input channels are grouped in channel groups, you must take into
account the conversion time channel group by channel group.
Example
Two analog input channels of the analog input module SM 331; AI 2 12 bits are
combined to form a channel group. You must therefore grade the scan time in
steps of 2.
Setting smoothing of analog values
You can set the smoothing of the analog values in STEP 7 for some analog input
modules.
Using smoothing
Smoothing of analog values ensures a stable analog signal for further processing.
It makes sense to smooth the analog values with slow variations of measured
values – for example, with temperature measurements.
Smoothing principle
The measured values are smoothed by digital filtering. Smoothing is accomplished
by the module calculating average values from a defined number of converted
(digitized) analog values.
The user assigns parameters to smoothing at not more than four levels (none, low,
average, high). The level determines the number of analog signals used for
averaging.
The higher the smoothing level chosen, the more stable is the smoothed analog
value and the longer it takes until the smoothed analog signal is applied after a
step response (refer to the following example).

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals