n
F1-30: PG Option Card Port for Motor 2 Selection
Specifies the drive port for the PG option card used for motor 2. Set this parameter when switching between motor 1 and motor
2, where both motors supply a speed feedback signal to the drive. Set F1-30 to 0 when using the same PG card for feedback
signals from both motors. Set F1-30 to 1 when each motor has its own PG card connected to the drive.
Note: The motor 2 selection function cannot be used with PM motors.
No. Parameter Name Setting Range Default
F1-30 PG Option Card Port for Motor 2 Selection 0, 1 1
Setting 0: CN5-C
Setting 1: CN5-B
u
F2: Analog Input Card Settings
These parameters set the drive for operation with the analog input option card AI-A3. This section describes parameters that
govern operation with an input option card. Refer to the option card instruction manual for specific details on installation,
wiring, input signal level selection, and parameter setup.
n
F2-01: Analog Input Option Card Operation Selection
Determines how the input terminals on the AI-A3 option card are used.
No. Parameter Name Setting Range Default
F2-01 Analog Input Option Card Operation Selection 0, 1 0
Setting 0: Separate functions for each terminal (V1, V2, V3 replace terminals A1, A2, A3)
Use the H3-oo parameters described in H3-03, H3-04: Terminal A1 Gain and Bias Settings on page 228 to set the functions
and gain and bias levels for an analog reference supplied by AI-A3.
Note: Setting option card terminals for separate input functions (F2-01 = 0) while b1-01 = 3 will cause an oPE05 error.
Setting 1: Combine input terminal values to create frequency reference
This setting adds all three input signals on the AI-A3 option card to create the frequency reference. Set b1-01 to 3 when the
option card is the source of the frequency reference for the drive. Set the gain and bias settings for the frequency reference
supplied from AI-A3 with F2-02 and F2-03.
n
F2-02, F2-03: Analog Input Option Card Gain, Bias
Parameter F2-02 sets the gain and parameter F2-03 sets the bias for the AI-A3 input signal when the card is used in the combined
input signals mode (F2-01 = 1). Both gain and bias are set as a percentage of the maximum output frequency.
No. Parameter Name Setting Range Default
F2-02 Analog Input Option Card Gain -999.9 to 999.9% 100.0%
F2-03 Analog Input Option Card Bias -999.9 to 999.9% 0.0%
Note: Enabled only when F2-01 = 1.
u
F3: Digital Input Card Settings
These parameters set the drive for operation with the option card DI-A3. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F3-01: Digital Input Option Card Input Selection
Determines the type of input for digital option card DI-A3 when o1-03 is set to 0 or 1.
No. Parameter Name Setting Range Default
F3-01 Digital Input Option Card Input Selection 0 to 7 0
Note: BCD input when o1-03 = 2 or 3. Units are determined by o1-03.
Setting 0: BCD, 1% units
Setting 1: BCD, 0.1% units
5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
199
5
Parameter Details