F6-08: Reset Communication Parameters
Determines whether F6-oo communication-related parameters are reset after initialization.
No. Parameter Name Setting Range Default
F6-08 Reset Communication Parameters 0, 1 0
Setting 0: Do not reset F6-oo parameters after initialization using A1-03
Setting 1: Reset F6-oo parameters after initialization using A1-03
Note:
F6-08 is not reset when the drive is initialized, but does determine whether initializing the drive resets the other F6-oo communication
parameters.
u
CC-Link Parameters
Parameters F6-04, F6-10, F6-11, and F6-14 set the drive to operate on a CC-Link network.
n
F6-04: bUS Error Detection Time
Sets the delay time for bUS error detection.
No. Parameter Name Setting Range Default
F6-04 bUS Error Detection Time 0.0 to 5.0 s 2.0 s
n
F6-10: CC-Link Node Address
Sets the node address of a CC-Link option board.
No. Parameter Name Setting Range Default
F6-10 CC-Link Node Address 0 to 64 0
n
F6-11: CC-Link Communication Speed
Sets the communication speed for a CC-Link option card.
No. Parameter Name Setting Range Default
F6-11 CC-Link Communication Speed 0 to 4 0
Settings:
F6-11 Communication Speed F6-11 Communication Speed
0 156 kbps 3 5 Mbps
1 625 kbps 4 10 Mbps
2 2.5 Mbps
n
F6-14: CC-Link bUS Error Auto Reset
Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.
No. Parameter Name Setting Range Default
F6-14 CC-Link bUS Error Auto Reset 0, 1 0
Setting 0: Disabled, auto reset not possible
Setting 1: Enabled, auto reset possible
u
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set the drive to run on a PROFIBUS-DP network.
n
F6-30: PROFIBUS-DP Node Address
Sets the node address of a PROFIBUS-DP option card.
No. Parameter Name Setting Range Default
F6-30 PROFIBUS-DP Node Address 0 to 125 0
5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
203
5
Parameter Details