n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
No. Parameter Name Setting Range Default
F6-01 Communications Error Operation Selection 0 to 3 1
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (continue operation)
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No. Parameter Name Setting Range Default
F6-02 External Fault from Comm. Option Detection Selection 0, 1 0
Setting 0: Always detected
Setting 1: Detection during run only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines drive operation when an external fault is initiated by a communication option (EF0).
No. Parameter Name Setting Range Default
F6-03 External Fault from Comm. Option Operation Selection 0 to 3 1
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
n
F6-06: Torque Reference/Torque Limit Selection from Comm. Option
Selects whether torque reference and torque limit values are assigned to the drive from the network.
No. Parameter Name Setting Range Default
F6-06 Torque Reference/Torque Limit Selection from Comm. Option 0, 1 0
Setting 0: Enabled
Setting 1: Disabled
n
F6-07: NetRef/ComRef Function Selection
Selects the treatment of multi-step speed inputs when the NetRef command is set.
No. Parameter Name Setting Range Default
F6-07 NetRef/ComRef Function Selection 0, 1 0
Setting 0: Multi-step speed operation disabled
Multi-step speed input frequency references are disabled when the NetRef command is selected.
Setting 1: Multi-step speed operation enabled
Multi-step speed inputs are still active and can override the frequency reference from the communications option even when
the NetRef command is selected.
5.6 F: Option Settings
202
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA AC Drive-A1000 and is the answer not in the manual?

YASKAWA AC Drive-A1000 Specifications

General IconGeneral
BrandYASKAWA
ModelAC Drive-A1000
CategoryController
LanguageEnglish

Related product manuals