A.4 Drive Watt Loss Data
Table A.3 Watt Loss Three-Phase 600 V Class Models
Model Number
CIMR-Ao
Normal Duty Heavy Duty
Rated Amps
(A)
<1>
Heatsink
Loss (W)
Interior Unit
Loss (W)
Total Loss
(W)
Rated Amps
(A)
<2>
Heatsink
Loss (W)
Interior Unit
Loss (W)
Total Loss
(W)
5A0003 2.7 21.5 23.3 44.8 1.7 28.9 19.8 48.7
5A0004 3.9 27.5 33.6 61.1 3.5 54.3 27.6 81.9
5A0006 6.1 28.1 43.7 71.8 4.1 53.0 27.0 80.0
5A0009 9.0 43.4 68.9 112.3 6.3 78.7 36.4 115.1
5A0011 11 56.1 88.0 144.0 9.8 110.9 49.5 160.3
5A0017 17 96.6 146.7 243.2 12.5 144.7 67.5 212.2
5A0022 22 99.4 178.3 277.7 17 203.8 81.1 284.8
5A0027 27 132.1 227.2 359.3 22 267.2 113.8 381.1
5A0032 32 141.6 279.9 421.5 27 332.9 132.2 465.1
<1> These values assume the carrier frequency is set to 2 kHz.
<2> These values assume the carrier frequency is set to 8 kHz.
A.4 Drive Watt Loss Data
376
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual