YASKAWA AC Drive-A1000 - L5: Fault Restart; L6: Torque Detection

YASKAWA AC Drive-A1000
534 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name Description Values Page
L4-06
(4C2)
Frequency Reference at
Reference Loss
All Modes
Sets the percentage of the frequency reference that the drive should run with
when the frequency reference is lost.
Default: 80%
Min.: 0.0
Max.: 100.0
257
L4-07
(470)
Speed Agreement Detection
Selection
All Modes
0: No detection during baseblock.
1: Detection always enabled.
Default: 0
Range: 0, 1
257
<1> Default setting is dependent on parameter A1-02, Control Mode Selection.
u
L5: Fault Restart
No.
(Addr.
Hex)
Name Description Values Page
L5-01
(49E)
Number of Auto Restart
Attempts
All Modes
Sets the number of times the drive may attempt to restart after the following
faults occur: GF, LF, oC, ov, PF, rH, rr, oL1, oL2, oL3, oL4, STo, Uv1.
Default: 0
Min.: 0
Max.: 10
258
L5-02
(49F)
Auto Restart Fault Output
Operation Selection
All Modes
0: Fault output not active.
1: Fault output active during restart attempt.
Default: 0
Range: 0, 1
258
L5-04
(46C)
Fault Reset Interval Time
All Modes
Sets the amount of time to wait between performing fault restarts.
Default: 10.0 s
Min.: 0.5
Max.: 600.0
258
L5-05
(467)
Fault Reset Operation
Selection
All Modes
0: Continuously attempt to restart while incrementing restart counter only at
a successful restarts (same as F7 and G7).
1: Attempt to restart with the interval time set in L5-04 and increment the
restart counter with each attempt (same as V7).
Default: 0
Range: 0, 1
258
u
L6: Torque Detection
No.
(Addr.
Hex)
Name Description Values Page
L6-01
(4A1)
Torque Detection
Selection 1
All Modes
0: Disabled
1: oL3 detection only active during speed agree, operation continues after
detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3
fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after
detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3
fault
8: UL3 detection always active during run, output shuts down on an oL3 fault
Default: 0
Range: 0 to 8
259
L6-02
(4A2)
Torque Detection
Level 1
All Modes
Sets the overtorque and undertorque detection level.
Default: 150%
Min.: 0
Max.: 300
260
L6-03
(4A3)
Torque Detection
Time 1
All Modes
Sets the time an overtorque or undertorque condition must exist to trigger
torque detection 1.
Default: 0.1 s
Min.: 0.0
Max.: 10.0
260
B.10 L: Protection Function
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
431