B.8 F: Options
F parameters program the drive for PG feedback from the motor and to function with option cards.
u
F1: PG Speed Control Card (PG-B3/PG-X3)
OLV/PMOLV/PM AOLV/PMAOLV/PM CLV/PMCLV/PM
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Parameters F1-01, F1-05, F1-06, F1-12, F1-13, and F1-18 through F1-21 include “PG 1” in the parameter name and are used
to set up a PG option card plugged into option port CN5-C of the drive.
Parameters F1-21 through F1-37 include “PG 2” in the parameter name and are used to set up a PG option card plugged into
option port CN5-B of the drive.
Other parameters in the F1 group are used to set operation for PG options plugged into port CN5-C and CN5-B.
No.
(Addr.
Hex)
Name Description Values Page
F1-01
(380)
PG 1 Pulses Per Revolution
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLV
Sets the number of PG (pulse generator or encoder) pulses. Sets the number
of pulses per motor revolution.
Default: 1024
Min.: 0
Max.: 60000
196
F1-02
(381)
Operation Selection at PG
Open Circuit (PGo)
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLV
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
4: No alarm display
Note: Due to potential damage to the motor and machinery, only use the
“Alarm only” and “No alarm display” settings under special
circumstances.
Default: 1
Range: 0 to 4
196
F1-03
(382)
Operation Selection at
Overspeed (oS)
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLV
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
196
F1-04
(383)
Operation Selection at
Deviation
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
AOLV/PM CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
AOLV/PM CLV/PM
CLV
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
Default: 3
Range: 0 to 3
197
F1-05
(384)
PG 1 Rotation Selection
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLV
0: Pulse A leads
1: Pulse B leads
Default:
<1>
Range: 0, 1
197
F1-06
(385)
PG 1 Division Rate for PG
Pulse Monitor
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
CLV/PM
CLV
Sets the division ratio for the pulse monitor used of the PG option card installed
to port CN5-C.
By setting “xyz”, the division ratio becomes = [(1 + x) / yz].
If only using the A pulse for one-track input, the input ratio will be 1:1
regardless of F1-06 setting.
Default: 1
Min.: 1
Max.: 132
197
F1-08
(387)
Overspeed Detection Level
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
AOLV/PM CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
AOLV/PM CLV/PM
CLV
Sets the overspeed detection level as a percentage of the maximum output
frequency.
Default: 115%
Min.: 0
Max.: 120
196
B.8 F: Options
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
407
B
Parameter List

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA AC Drive-A1000 and is the answer not in the manual?

YASKAWA AC Drive-A1000 Specifications

General IconGeneral
BrandYASKAWA
ModelAC Drive-A1000
CategoryController
LanguageEnglish

Related product manuals