EasyManua.ls Logo

YASKAWA AC Drive-A1000 - U: Monitors; U1: Operation Status Monitors

YASKAWA AC Drive-A1000
534 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B.15 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
u
U1: Operation Status Monitors
OLV/PMOLV/PM AOLV/PMAOLV/PM CLV/PMCLV/PM
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
No.
(Addr.
Hex)
Name Description
Analog Output
Level
Unit
U1-01
(40)
Frequency Reference
All Modes
Monitors the frequency reference. Display units are determined by o1-03.
10 V: Max frequency 0.01 Hz
U1-02
(41)
Output Frequency
All Modes
Displays the output frequency. Display units are determined by o1-03.
10 V: Max frequency 0.01 Hz
U1-03
(42)
Output Current
All Modes
Displays the output current.
10 V: Drive rated
current
<1>
<2>
U1-04
(43)
Control Method
All Modes
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
No signal output
available
U1-05
(44)
Motor Speed
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Displays the motor speed feedback. Display units are determined by o1-03.
10 V: Max Frequency 0.01 Hz
U1-06
(45)
Output Voltage Reference
All Modes
Displays the output voltage.
10 V: 575 Vrms 0.1 Vac
U1-07
(46)
DC Bus Voltage
All Modes
Displays the DC bus voltage.
10 V: 1150 V 1 Vdc
U1-08
(47)
Output Power
All Modes
Displays the output power (this value is calculated internally).
10 V: Drive rated power
(kW)
<3>
U1-09
(48)
Torque Reference
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
OLV
CLV/PM
CLV
Monitors the internal torque reference.
10 V: Motor rated
torque
0.1%
U1-10
(49)
Input Terminal Status
All Modes
Displays the input terminal status.
U1
-
10=
00000000
Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
1
1
1
1
1
1
1
1
No signal output
available
B.15 U: Monitors
448
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual

Table of Contents

Related product manuals