Table 5.37 LO/RE Key and b1-07
o2-01 b1-07 Switch from LOCAL to REMOTE Switch from REMOTE to LOCAL
0
0 Not possible Not possible
1 Not possible Not possible
1
0
Will not run until a new Run command is
entered.
Run not possible
1
If a Run command is entered, the drive will start
running as soon as the LO/RE key is pushed to
change from LOCAL to REMOTE.
Run not possible
n
o2-02: STOP Key Function Selection
Determines if the STOP key on the digital operator will stop drive operation when the drive is controlled from a remote source
(i.e., not from digital operator).
No. Name Setting Range Default
o2-02 STOP Key Function Selection 0, 1 1
Setting 0: Disabled
Setting 1: Enabled
The STOP key will terminate drive operation even if the Run command source is not assigned to the digital operator. Cycle
the Run command to restart the drive if the drive has been stopped by pressing the STOP key.
n
o2-03: User Parameter Default Value
After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,
parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parameters
to the user-set default values. Refer to A1-03: Initialize Parameters on page 121 for details on drive initialization.
No. Name Setting Range Default
o2-03 User Parameter Default Value 0 to 2 0
Setting 0: No change (awaiting command)
Setting 1: Set User Initialize values
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the
ENTER key saves the values and returns the display to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for “User Initialize” are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values and
returns the display to 0.
n
o2-04: Drive Model Selection
Seth this parameter when replacing the control board or the terminal board. Refer to Defaults by Drive Model (o2-04) and
ND/HD (C6-01) on page 460 for information on drive model selection.
NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.
No. Name Setting Range Default
o2-04 Drive Model Selection -
Determined by
drive capacity
n
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in the
Drive Mode.
No. Name Setting Range Default
o2-05 Frequency Reference Setting Method Selection 0, 1 0
Setting 0: ENTER key required
The ENTER key must be pressed every time the frequency reference is changed using the digital operator for the drive to
accept the change.
5.10 o: Operator Related Settings
280
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual