EasyManua.ls Logo

YASKAWA AC Drive-A1000 - Page 421

YASKAWA AC Drive-A1000
534 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function Description Page
30 During torque limit
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
OLV
CLV/PM
CLV
Closed: When the torque limit has been reached.
225
31 During speed limit
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Closed: Speed limit has been reached.
226
32
During speed limit in Torque
Control
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Closed: Speed limit has been reached while using Torque Control.
226
33 Zero Servo complete
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Closed: Zero Servo operation has finished.
226
37 During frequency output
All Modes
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being
performed).
226
38 Drive enabled
All Modes
Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A).
226
39 Watt hour pulse output
All Modes
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
226
3C LOCAL/REMOTE status
All Modes
Open: REMOTE
Closed: LOCAL
226
3D During speed search
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Closed: Speed Search is being executed.
227
3E PID feedback low
All Modes
Closed: PID feedback level is too low.
227
3F PID feedback high
All Modes
Closed: The PID feedback level is too high.
227
4A During KEB Ride-Thru
All Modes
Closed: KEB Ride-Thru is being performed.
227
4B During short circuit braking
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Closed: Short Circuit Braking is active.
227
4C During fast stop
All Modes
Closed: A Fast Stop command has been entered from the operator or input terminals.
227
4D oH Pre-alarm time limit
All Modes
Closed: oH pre-alarm time limit has passed.
227
4E Braking transistor fault (rr)
All Modes
Closed: The built-in dynamic braking transistor failed.
227
4F Braking resistor overheat (oH)
All Modes
Closed: The dynamic braking resistor has overheated.
227
60 Internal cooling fan alarm
All Modes
Closed: Internal cooling fan alarm
227
61
Rotor position detection
complete
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM CLV/PM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM CLV/PM
Closed: Drive has successfully detected the rotor position of the PM motor.
227
B.9 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
421
B
Parameter List

Table of Contents