EasyManuals Logo

YASKAWA AC Drive-A1000 User Manual

YASKAWA AC Drive-A1000
534 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #470 background imageLoading...
Page #470 background image
n
H5-11: Communications Enter Function Selection
Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications. Refer
to Enter Command on page 492.
No. Name Setting Range Default
H5-11 Communications Enter Function Selection 0 or 1 1
Setting 0: Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
n
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02, b1-16 = 2).
No. Name Setting Range Default
H5-12 Run Command Method Selection 0 or 1 0
Setting 0: FWD/Stop, REV/Stop
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive in the forward direction. Setting bit 1 will start and
stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive. Setting bit 1 changes the direction.
C.4 MEMOBUS/Modbus Setup Parameters
470
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA AC Drive-A1000 and is the answer not in the manual?

YASKAWA AC Drive-A1000 Specifications

General IconGeneral
BrandYASKAWA
ModelAC Drive-A1000
CategoryController
LanguageEnglish

Related product manuals