No. Item Page
25 Ensure that no frayed wires on the terminal block are touching other terminals or connections.
26 Properly separate control circuit wiring and main circuit wiring.
27 Analog signal line wiring should not exceed 50 m.
28
Safe Disable input wiring should not exceed 30 m.
<1>
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, EN954-1/ISO13849
Cat. 3, IEC/EN61508 SIL2, Insulation coordination: class 1.
3.13 Wiring Checklist
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual