8 System Setup
8.22Break Line Ground Judgment Function
8-197
182582-1CD
182582-1CD
MH900, DX200 Controller
2. Press “YES”.
– The confirmation dialog appears due to prevent the mis-operation.
– Select “YES”, then the break line ground check appears.
– Select “NO”, the window returns to the previous window.
3. Move the cursor over the axis to perform the break line ground check,
and press [SERVO ON READY]. Grip the enable switch and long
press [SELECT] while pressing down the [INTER LOCK] to perform
the break line ground check.
– Perform the break line ground check to the every single axis
displayed on the screen.
– The break line ground check is canceled in the case of following
conditions.
• [SELECT] is detached.
• The emergency button of the programming pendant, controller or
external signal is pressed.
• The servo power is disconnected by the servo power supply
individual control function.
• The servo alarm occurs.
JUDGMENT REQUIRED: The ground check is not performed
BREAKS LINE NORMAL: The break line is normal.