8 System Setup
8.23Safety Logic Circuit
MH900, DX200 Controller
– The confirmation dialog appears, and select {YES}.
– The safety logic circuit file(file name: YSFLOGIC.DAT) written in the
FLASH ROM of the machine safety circuit board (type: YSF21-E) is
erased.
Machine Safety FLASH Reset
1. Displaying the window.
– Select {Machine Safety Board FLASH Reset} by going to
{INITIALIZE} from {FILE} in the man menu.
– The confirmation dialog appears, and select {YES}.
– The safety logic circuit file (file name: YSFLOGIC.DAT) is
transferred and written in the FLASH ROM of the machine safety
circuit board (type: YSF21-E).
After performing the “Machine Safety Board FLASH Erase”,
and turning the controller power supply ON/OFF. Next time
when turning the power supply ON, the alarm “0300:
VERIFY ERROR (SYSTEM CONFIG-DATA)” occurs.
Therefore, when performing the “Machine Safety Board
FLASH Erase”, the “Machine Safety FLASH Restart” needs
to be performed as well.