No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
b1-08
Run Command Selection
while in Programming Mode
0: Run command accepted only in the operation menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during Run
0 to 2 0 A A A 187 122
b1-14 Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2
and W/T3.
0 : Standard
1 : Switch phase order
0, 1 0 A A A 1C3 123
b1-15
Frequency Reference
Selection 2
Selects the frequency reference input source 2.
0: Operator - Digital preset speed d1-01 to d1-17.
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4 0 A A A 1C4 123
b1-16 Run Command Selection 2
Selects the run command input source 2.
0: Operator - RUN and STOP keys on the digital operator.
1: Digital input terminals
2: MEMOBUS communications
3: Option PCB
0 to 3 0 A A A 1C5 123
b1-17
Run Command at Power
Up
Determines the operation when a Run command is active at
power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
0, 1 0 A A A 1C6 123
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
b2-01
DC Injection Braking Start
Frequency
Sets the frequency at which DC Injection Braking starts
when Ramp to Stop (b1-03 = 0) is selected. If b2-01< E1-09,
DC Injection Braking starts at E1-09.
0.0 to
10.0
0.5
Hz
A A A 189 123
b2-02
DC Injection Braking
Current
Sets the DC Injection Braking current as a percentage of the
drive rated current.
0 to 75 50% A A A 18A 124
b2-03
DC Injection Braking Time/
DC Excitation Time at
Start
Sets DC Injection Braking time at start. Disabled when set
to 0.00 seconds.
0.00 to
10.00
0.00 s
<1>
A A A 18B 124
b2-04
DC Injection Braking Time
at Stop
Sets DC Injection Braking time at stop.
When b1-03 = 2, actual DC Injection time is calculated as
follows:
(b2-04)
x 10 x (Output Freq)/(E1-04). When b1-03 = 0, this
parameter sets the amount of DC Injection time applied to
the motor at the end of the decel ramp or High Slip Braking.
Disabled when set to 0.00.
0.00 to
10.00
0.50 s A A − 18C 124
b2-08
Magnetic Flux
Compensation Value
Sets the magnetic flux compensation as a percentage of the
no-load current value (E2-03).
0 to 1000 0% − A − 190 124
b2-12
Short Circuit Brake Time at
Start
Sets the time for Short-Circuit brake operation at start.
Disabled when set to 0.00.
<2>
0.00 to
25.50
0.00 s − − A 1BA 124
b2-13
Short Circuit Brake Time at
Stop
Sets the Short-Circuit brake operation time at stop. Used to
stop
a motor rotating due to inertia. Disabled
when set to 0.00
seconds.
<2>
0.00 to
25.50
0.50 s − − A 1BB 125
b3: Speed Search
Use b3 parameters to configure Speed Search function operation.
b3-01
Speed Search Selection at
Start
Enables/disables the Speed Search function at start.
0: Disabled - Speed Search is not automatically performed
at start.
1: Enabled - Speed Search is automatically performed at
start.
0, 1 0 A A A 191 128
b3-02
Speed Search Deactivation
Current
Sets the current level at which the speed is assumed to be
detected and Speed Search is ended. Set as a percentage of
the drive rated current.
0 to 200
120
<3>
A A − 192 128
b3-03
Speed Search Deceleration
Time
Sets the time constant used to reduce the output frequency
during
Speed Search. Related to a change from
max. output
frequency to 0.
0.1 to
10.0
2.0 s A A − 193 128
b3-05 Speed Search Delay Time
Delays the Speed Search operation after a momentary power
loss to allow time for an external output contactor to close.
0.0 to 100 0.2 s A A A 195 128
b3-06
Output Current 1 during
Speed Search
Sets the current injected to the motor at the beginning of
Estimation type Speed Search. Set as a factor of the motor
rated current.
0.0 to 2.0
<4>
A A − 196 128
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
333