<6. Parameter Lists>
173
IM 01E21A02-03EN
Relative
Index
Index Parameter Name Default Value
Write
Mode
Description
56 1056
FD_CHECK_
MASK
0x00000000 AUTO
Speciesabitnottonotifytothehost
among32-bit“CheckFunction”alarms
appearingonFD_CHECK_ACTIVE.For
detailsaboutbitassignment,referto■
Field Diagnostic.
57 1057 FD_FAIL_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when the
alarmclassiedinto“Failed”occurs.
58 1058
FD_OFFSPEC_
ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when the
alarmclassiedinto“OSpecication”
occurs. For details about bit assignment,
refer to FD and bit items in the table in
Subsection 5.6.2.
59 1059 FD_MAINT_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when
thealarmclassiedinto“Maintenance”
occurs.
60 1060 FD_CHECK_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when the
alarmclassiedinto“CheckFunction”
occurs.
61 1061 FD_FAIL_PRI 0 AUTO
Indicates the FD_FAIL_ALM priority
of the alarm. To activate an alarm
on communication, it is necessary
to specify the priority for alarm
activation in advance. To activate an
alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
toapplyaltertoignorevaluesbelow
thespeciedpriorityonthehostside.
62 1062
FD_OFFSPEC_
PRI
0 AUTO
Indicates the FD_OFFSPEC_ALM
priority of the alarm. To activate an
alarm on communication, it is necessary
to specify the priority for alarm
activation in advance. To activate an
alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
toapplyaltertoignorevaluesbelow
thespeciedpriorityonthehostside.
63 1063 FD_MAINT_PRI 0 AUTO
Indicates the FD_MAINT_ALM priority
of the alarm. To activate an alarm
on communication, it is necessary
to specify the priority for alarm
activation in advance. To activate an
alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
toapplyaltertoignorevaluesbelow
thespeciedpriorityonthehostside.