<Appendix 4. Link Master Functions>
277
IM 01E21A02-03EN
Q4. “AL.20” remains displayed on LCD.
The reason could be that LAS may not be on the bus, that communication with LAS is not
established, and so on.
A4-1. CheckthatLASisconnectedtothebus.(TousethisproductasLAS,performthe
followingoperationsinA4.3(1),(2)and(3).)
A4-2. SettheLASparametertotheoperatingparameterofthisproduct.(Reference:4.2
Networkdenition)
LAS This product
V(ST) > V(ST) (4ormore)
V(MID) > V(MID) (4ormore)
V(MRD) > V(MRD) (3ormore)
A4-3. Checkthattheaddressofthisproductiscorrect.(Reference:4.2NetworkDenition)
The address of this product is;
• OutsidetheLASparameterV(FUN)toV(FUN)+V(NUN).
• Notthedefaultaddress(0xF8to0xFB).