<5. Functions>
95
IM 01E21A02-03EN
NE
107
Error Message
Error Description Countermeasure FD bit
Display
F
OUNDATION
Fieldbus
C 329:PID Man Mode PID in Man Mode
The PID block is in the
Man mode.
Change the PID block
mode.
6 14
C 330:PID Not Schedule PID Not Scheduled
The PID block is
unscheduled.
Schedule the PID
block.
6 13
C 331:PID Bypass Mode PID in Bypass Mode
2.ON is selected by
BYPASS of PID.
Set BYPASS to 1.OFF. 6 12
C 332:IT1 O/S mode IT1 in O/S Mode
The IT1 block is in the
O/S mode.
Change the IT1 block
mode.
6 11
C 333:IT1 Man mode IT1 in Man Mode
The IT1 block is in the
Man mode.
Change the IT1 block
mode.
6 10
C 334:IT1 Not Schedule IT1 Not Scheduled
IT1 block is
unscheduled.
Schedule the IT1 block. 6 9
C 336:IT2 O/S Mode IT2 in O/S Mode
The IT2 block is in the
O/S mode.
Change the IT2 block
mode.
6 7
C 337:IT2 Man Mode IT2 in Man Mode
The IT2 block is in the
Man mode.
Change the IT2 block
mode.
6 6
C 338:IT2 Not Schedule IT2 Not Scheduled
IT2 block is
unscheduled.
Schedule the IT2 block. 6 5
C 340:DI1 O/S Mode DI1 in O/S Mode
The DI1 block is in the
O/S mode.
Change the DI1 block
mode.
6 3
C 341:DI1 Man Mode DI1 in Man Mode
The DI1 block is in the
Man mode.
Change the DI1 block
mode.
6 2
C 342:DI1 Not Schedule DI1 Not Scheduled
DI1 block is
unscheduled.
Schedule the DI1
block.
6 1
C 343:DI1 Simulate Act
DI1 Simulation
Active
DI1 simulation function
is running.
Disable SIMULATE.
Simulate En/Disable of
the DI1 block.
6 0
C 344:DI2 O/S Mode DI2 in O/S Mode
The DI2 block is in the
O/S mode.
Change the DI2 block
mode.
7 31
C 345:DI2 Man Mode DI2 in Man Mode
The DI2 block is in the
Man mode.
Change the DI2 block
mode.
7 30
C 346:DI2 Not Schedule DI2 Not Scheduled
DI2 block is
unscheduled.
Schedule the DI2
block.
7 29
C 347:DI2 Simulate Act
DI2 Simulation
Active
DI2 simulation function
is running.
Disable SIMULATE.
Simulate En/Disable of
the DI2 block.
7 28
C 348:DI3 O/S Mode DI3 in O/S Mode
The DI3 block is in the
O/S mode.
Change the DI3 block
mode.
7 27
C 349:DI3 Man Mode DI3 in Man Mode
The DI3 block is in the
Man mode.
Change the DI3 block
mode.
7 26
C 350:DI3 Not Schedule DI3 Not Scheduled
DI3 block is
unscheduled.
Schedule the DI3
block.
7 25
C 351:DI3 Simulate Act
DI3 Simulation
Active
DI3 simulation function
is running.
Disable SIMULATE.
Simulate En/Disable of
the DI3 block.
7 24
C 352:AR O/S Mode AR in O/S Mode
The AR block is in the
O/S mode.
Change the AR block
mode.
7 23
C 353:AR Man Mode AR in MAN Mode
The AR block is in the
Man mode.
Change the AR block
mode.
7 22
C 354:AR Not Scheduled AR Not Scheduled
The AR block is
unscheduled.
Schedule the AR block. 7 21
C 356:MAO O/S Mode MAO in O/S Mode
The MAO block is in
the O/S mode.
Change the MAO block
mode.
7 19
C 357:MAO NotSchedule MAO Not Scheduled
The MAO block is
unscheduled.
Schedule the MAO
block.
7 18
C 359:No FB Scheduled No FB Scheduled
No function block is
scheduled.
Check the schedule of
LAS communication or
function block.
7 16
C 360:SnsrTB O/S Mode
Sensor TB in O/S
Mode
The STB block is in the
O/S mode.
Change the STB block
mode.
7 15

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?

YOKOGAWA ADMAG TI Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG TI Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals