118 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 4 System Operation and Configuration
Analog I/O Expansion
Modules
The E300 relay supports up to four Analog I/O Expansion Modules on the E300
Expansion Bus. The E300 Analog Expansion Module has three independent
universal inputs and one analog output.
Analog Input Channels
The universal analog inputs can accept the following analog signals:
Current
4…20 mA
0…20 mA
Vo
l t ag e
0…10V DC
1…5V
DC
0…5V
DC
2-Wi
re or 3-Wire RTD Sensors
100 Ω, 200
Ω, 500 Ω,
1000 Ω Pt 385
100 Ω, 200 Ω, 500 Ω,
1000 Ω Pt 3916
10 Ω Cu 426
100 Ω Ni 618
120 Ω Ni 672
604 Ω NiFe 518
Resistance
0…150
Ω
0…750 Ω
0…3000
Ω
0…6000 Ω (PTC
and NTC Sensors)
The analog inputs can report data in four different formats. Table 122 through
Table 125
display the data ranges for all of the available analog input types for the
four available data formats.
Table 122 - Analog Input Data Format for Current Input Type
Input Range Input Value Condition
Engineering
Units
Engineering
Units x 10
Raw /
Proportional
PID
4…20 mA
21.00 mA High Limit 21000 2100 32767 17407
20.00 mA High Range 20000 2000 32767 16383
4.00 mA Low Range 4000 400 -32768 0
3.00 mA Low Limit 3000 300 -32768 -1024
0…20 mA
21.00 mA High Limit 21000 2100 32767 17202
20.00 mA High Range 20000 2000 32767 16383
0.00 mA Low Range 0 0 -32768 0
0.00 mA Low Limit 0 0 -32768 0

Table of Contents

Other manuals for Allen-Bradley E300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley E300 and is the answer not in the manual?

Allen-Bradley E300 Specifications

General IconGeneral
TypeElectronic Overload Relay
MountingDIN Rail or Panel Mount
Protection ClassIP20
Voltage Range24…690 V AC/DC
Communication OptionsEtherNet/IP, DeviceNet
ProtectionOverload, phase loss, ground fault
Operating Temperature-20°C to 60°C