Rockwell Automation Publication 193-UM015E-EN-P - October 2015 287
Operating Modes Chapter 5
Two-speed Starter (Local I/O) – Three-wire Control
The E300 relay’s Operating Mode Two Speed Starter (Local I/O) – Three Wire
Control (Parameter 195 = 48) uses a normally open momentary push button in
Input 0 to energize Output Relay 0, which controls the high-speed contactor coil.
A normally open momentary push button in Input 1 is used to energize Output
Relay 1, which controls the low-speed contactor coil. A normally closed push
button in Input 2 is used to de-energize Output Relay 0 and Output Relay 1.
Both Input 0, Input 1, and Input 2 are momentary signals, so the two-speed
starter only energizes if Input 2 is active and Input 0 or Input 1 is momentarily
active.
InterlockDelay (Parameter 215) defines the minimum time delay when switching
direction.
The reset button of the E300 Operator Station is enabled for this operating
mode.
Rules
1. Available for Control Module firmware v5.000 and higher.
2. Four digital inputs must be available on the Control Module
3. Output Pt00 Assignment (Parameters 202) must be set to Control Relay.
4. Output Pt00 Assignment (Parameters 202) must be set to Control Relay.
5. Overload Trip must be enabled in TripEnableI (Parameter 183).
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Figure 190 is a wiring diagram of a Two-speed Starter with three-wire control and
Output Relay 0 and Output Relay 1 configured as control relays.
Figure 190 - Two-speed Starter (Local I/O) – Three-wire Control Wiring Diagram
R13 R14
Relay 0
Run Slow
E300
Control Power
R03 R04
Relay 0
Run Fast
Stop
IN 2
IN 1
Run Slow
IN 0
Run Fast