Chapter 7 Commands
Table 419 - Clear Command (Parameter 165)
Clear Operating Statistics
When the Clear Operating Statistics command is issued, the E300 relay sets the
following parameters to a value of zero (0):
Operating Time (Parameter 28)
Starts Counter (Parameter 29)
Clear History Logs
When the Clear History Logs command is issued, the E300 relay sets the
following parameters to a value of zero (0):
Trip History 0 (Parameter 127)
Trip History 1 (Parameter 128)
Trip History 2 (Parameter 129)
Trip History 3 (Parameter 130)
Trip History 4 (Parameter 131)
Warning History 0 (Parameter 132)
Warning History 1 (Parameter 133)
Warning History 2 (Parameter 134)
Warning History 3 (Parameter 135)
Warning History 4 (Parameter 136)
Default Value 0 = Ready
Range 0 = Ready
1 = Clear Operating Statistics
2 = Clear History Logs
3 = Clear %TCU
4 = Clear kWh
5 = Clear kVARh
6 = Clear kVAh
7 = Clear Max kW Demand
8 = Clear Max kVAR Demand
9 = Clear Max kVA Demand
10 = Clear All
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units

Table of Contents

Other manuals for Allen-Bradley E300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley E300 and is the answer not in the manual?

Allen-Bradley E300 Specifications

General IconGeneral
TypeElectronic Overload Relay
MountingDIN Rail or Panel Mount
Protection ClassIP20
Voltage Range24…690 V AC/DC
Communication OptionsEtherNet/IP, DeviceNet
ProtectionOverload, phase loss, ground fault
Operating Temperature-20°C to 60°C

Related product manuals