482 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 7 Commands
Table 419 - Clear Command (Parameter 165)
Clear Operating Statistics
When the Clear Operating Statistics command is issued, the E300 relay sets the
following parameters to a value of zero (0):
• Operating Time (Parameter 28)
• Starts Counter (Parameter 29)
Clear History Logs
When the Clear History Logs command is issued, the E300 relay sets the
following parameters to a value of zero (0):
• Trip History 0 (Parameter 127)
• Trip History 1 (Parameter 128)
• Trip History 2 (Parameter 129)
• Trip History 3 (Parameter 130)
• Trip History 4 (Parameter 131)
• Warning History 0 (Parameter 132)
• Warning History 1 (Parameter 133)
• Warning History 2 (Parameter 134)
• Warning History 3 (Parameter 135)
• Warning History 4 (Parameter 136)
Default Value 0 = Ready
Range 0 = Ready
1 = Clear Operating Statistics
2 = Clear History Logs
3 = Clear %TCU
4 = Clear kWh
5 = Clear kVARh
6 = Clear kVAh
7 = Clear Max kW Demand
8 = Clear Max kVAR Demand
9 = Clear Max kVA Demand
10 = Clear All
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units