EasyManua.ls Logo

Allen-Bradley E300 - Reversing Starter (Local I;O) - Two-Wire Control

Allen-Bradley E300
736 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
226 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 5 Operating Modes
Timing Diagram
Figure 131 - Reversing Starter (Operator Station) with Feedback Timing Diagram
Reversing Starter (Local I/O) – Two-wire Control
The E300 relay’s Operating Mode Reversing Starter (Local I/O) – Two Wire
Control (Parameter 195 = 40) uses Input 0 to control Output Relay 0, which
controls the contactor coil of the forward contactor, and Input 1 to control
Output Relay 1, which controls the contactor coil of the reversing contactor.
Both Input 0 and Input 1 are maintained signals, so the reversing starter remains
energized when either Input 0 or Input 1 is active. Both Input 0 and Input 1 must
be in a de-active state before changing to another direction
InterlockDelay (Parameter 215) defines the minimum time delay when switching
direction.
The reset button of the E300 Operator Station is enabled for this operating
mode.
Trip Event Feedback
Timeout
Forward
Stop
REV (Relay 1)
FWD (Relay 0)
Timer
Feedback
Timeout Trip
Trip Status
Trip Reset
Reverse
FWD Feedback
REV Feedback

Table of Contents

Other manuals for Allen-Bradley E300

Related product manuals