568 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 10 EtherNet/IP Communication
Resetting the System Password
If the password for user name Administrator is misplaced or forgotten, you can
restore the password to the factory default value by turning the rotary dials on the
E300 EtherNet/IP Communication Module to 8-8-8 and cycling power. This
resets all EtherNet/IP communication settings and E300 configuration
parameters back to the factory default values.
Permanently Enabling the Web Server
In Administrative Mode, you can change any configuration parameter of the
E300 relay including permanently enabling the embedded web server by
following these steps:
1. Enter Administrative Mode by turning the rotary dials to 000 and cycle
powe
r on the E300 relay.
2. Access the web page.
3. Navigate to Administrative Settings->Network Configuration.
4. You are prompted for a user name and password. Enter "Administrator" for
the
user name, and enter the appropriate password.