Operating Modes Chapter 5
Figure 158 - Reversing Starter (Network & Local I/O) – Three-wire Control DeviceLogix Program,
Part C
Reversing Starter (Custom)
The E300 relay’s Operating Mode Reversing Starter (Custom) (Parameter 195 =
51) operates as a reversing starter with two output relays that are assigned as
normally open control relays. The Reversing Starter (Custom) operating mode is
used for applications that want customized DeviceLogix programs. This
operating mode requires minimal configuration rules.
Rules
1. Available for Control Module firmware v5.000 and higher.
2. Set two of the Output Ptxx Assignments (Parameters 202…204) to
Contr
ol Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).