628 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Appendix A Specifications
Protection
Table 583 - Protection
Table 584 - Overload Protection
Table 585 - Ground Fault Protection (External Ground Fault Module)
Trip Warning
Overload Yes Yes
Phase Loss Yes No
Ground Fault Yes Yes
Stall Yes No
Jam Yes Yes
Underload Yes Yes
Thermistor (PTC) Yes Yes
Current Imbalance Yes Yes
Remote Trip Yes No
Blocked Start/Start Inhibit Yes No
Under Voltage L-L Yes Yes
Over Voltage L-L Yes Yes
Voltage Unbalance Yes Yes
Phase Rotation Yes Yes
Under Frequency Yes Yes
Over Frequency Yes Yes
Under Real Power (kW) Yes Yes
Over Real Power (kW) Yes Yes
Under Reactive Power Consumed (+kVAR) Yes Yes
Over Reactive Power Consumed (+kVAR) Yes Yes
Under Reactive Power Generated (-kVAR) Yes Yes
Over Reactive Power Generated (-kVAR) Yes Yes
Under Apparent Power (kVA) Yes Yes
Over Apparent Power (kVA) Yes Yes
Under Power Factor Lagging (-PF) Yes Yes
Over Power Factor Lagging (-PF) Yes Yes
Under Power Factor Leading (+PF) Yes Yes
Over Power Factor Leading (+PF) Yes Yes
Power Value Overflow (kW, kVAR or KVA) Yes Yes
Analog Over Level Yes Yes
Type of Relay
Ambient Compensated Time-Delay
Phase Loss Sensitive
Nature of Relay Solid-State
FLA Setting See Full Load Amps Setting on page 313
Trip Rating 120% FLA
Trip Class 5…30
Reset Mode Automatic or Manual
Overload Reset Level 1…100% TCU
Type Core Balanced
Intended Use Equipment Protection
Classification (Per UL 1053) Class I
Protection Range
20…100 mA
100…500 mA
200 mA…1.0 A
1.0…5.0 A
Trip and Warning Time Delay 0.1…25.0 s
Protection Inhibit Time 0…250 s