Rockwell Automation Publication 193-UM015E-EN-P - October 2015 195
Operating Modes Chapter 5
Figure 100 - Non-reversing Starter (Network & Local I/O) – Two-wire Control DeviceLogix Program
Timing Diagram
Figure 101 - Non-reversing Starter (Network & Local I/O) – Two-wire Control Timing Diagram
Non-reversing Starter (Network & Local I/O) with Feedback –
Two-wire Control
The E300 relay’s Operating Mode Non-Reversing Starter (Network & Local I/O)
with Feedback – Two Wire Control (Parameter 195 = 17) uses the network tag
LogicDefinedPt00Data in Output Assembly 144 in Remote control mode and
Input 2 in Local control mode to control Relay 0, which controls the contactor
coil. Input 3 determines whether the motor starter is in Remote or Local control
mode. LogicDefinedPt00Data is a maintained value, so the non-reversing starter
remains energized when LogicDefinedPt00Data has a value of 1 in Remote
control mode. You can program the appropriate state of the starter when
communication is lost in Remote control mode by using the Network
rip Status
Trip Reset
Trip Event
Run/Stop
Relay 0