Rockwell Automation Publication 193-UM015E-EN-P - October 2015 81
System Operation and Configuration Chapter 4
Enable Option Match Protection Trip (Parameter 186)
To enable the Option Match feature to cause a protection trip in the event of an
option mismatch, place a (1) in bit position 8 of Parameter 186 (Control Trip
Enable). You can select the specific option match features to cause a protection
trip in Parameter 233 (Option Match Action).
Table 30 - Enable Option Match Protection Trip Bit Function Detail— Control Trip Enable
(Parameter 186)
Bit
1514131211109876543210 Function
X Test Trip Enable
XPTC Trip Enable
X DeviceLogix Trip Enable
X Operator Station Trip Enable
X Remote Trip Enable
X Blocked Start Trip Enable
X Hardware Fault Trip Enable
X Configuration Trip Enable
X Option Match Trip Enable
X Feedback Timeout Trip Enable
X Expansion Bus Trip Enable
Reserved
Reserved
X Nonvolatile Memory Trip Enable
XReady
Reserved