EasyManua.ls Logo

Allen-Bradley E300 - Electromagnetic Compatibility Specifications

Allen-Bradley E300
736 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 193-UM015E-EN-P - October 2015 627
Specifications Appendix A
Electromagnetic
Compatibility Specifications
Performance Criteria 1 requires the DUT to experience no degradation or loss of performance.
Environment 2.
Table 582 - Electromagnetic Compatibility Specifications
Electrostatic Discharge Immunity
Test Level:
Performance Criteria:
8kV Air Discharge
6kV Contact Discharge
1 ➊➋
RF Immunity
Test Level:
Performance Criteria:
10V/m
1 ➊➋
Electrical Fast Transient/Burst Immunity
Test Level:
Performance Criteria:
4kV (Power)
2kV (Control and Comm)
1 ➊➋
Surge Immunity
Test Level:
Performance Criteria:
2kV (L-E)
1kV (L-L)
1 ➊➋
Radiated Emissions
Class A
Conducted Emissions
Class A