512 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 8 Metering and Diagnostics
Table 470 - L1-N Voltage (Parameter 57)
L2-N Voltage
L2-N Voltage (Parameter 58) reports the voltage in volts in reference to the T2
power terminal of the E300 relay Sensing Module.
Table 471 - L2-N Voltage (Parameter 58)
L3-N Voltage
L3-N Voltage (Parameter 59) reports the voltage in volts in reference to the T3
power terminal of the E300 relay Sensing Module.
Table 472 - L3-N Voltage (Parameter 59)
Average L-N Voltage
Average L-N Voltage (Parameter 60) reports the average voltage of the monitored
L-N voltages. When Single or Three Phase (Parameter 176) is set to Three Phase,
Average L-N Voltage is calculated as follows:
Average L-N Voltage = (L1-N Voltage + L2-N Voltage + L3-N Voltage) / 3
Default Value 0.0
Minimum Value 0.0
Maximum Value 6553.5
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 10
Units Volts
Default Value 0.0
Minimum Value 0.0
Maximum Value 6553.5
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 10
Units Volts
Default Value 0.0
Minimum Value 0.0
Maximum Value 6553.5
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 10
Units Volts