EasyManua.ls Logo

Allen-Bradley E300 - Environmental Specifications

Allen-Bradley E300
736 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
626 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Appendix A Specifications
Environmental Specifications
Current ratings must be derated at altitudes greater than 2000 m
Temperature rating based on 120V AC control module with 1 A going through relays 0, 1, and 2.
Temperature rating based on 24V DC control module with four digital inputs active and 0.2 A going through
relays 0, 1, and 2.
Temperature rating based on 120V AC or 240V AC control module with 5A going through relays 0, 1, and 2.
NOTE: The E300 relay expansion power supplies (Cat. Nos. 193-EXP-PS-AC
and 193-EXP-PS-DC) surrounding air temperature must not exceed 55 °C (131
°F).
Table 581 - Temperature Derating
Table 579 - Expansion Power Supply Modules
Expansion Power Supply Modules 193-EXP-PS-AC
Rated Operational Voltage (U
e
): 100…250V AC
Rated Insulation Voltage (U
i
): 2640Vrms for 1s
Rated Impulse Withstand Voltage (U
imp
): 4 kV
Conditional Short Circuit Current: N/A
Protection Against Short Circuits: N/A
Utilization Category: N/A
Pollution Degree: 3
Table 580 - Environmental Specifications
Ambient Temperature
Storage
Operating
(Open)
(Enclosed)
–40…+85 C (–40…+185 F)
–20…+55 C (–4…+131 F)➋➌
–20…+40 C (–4…+104 F)➌➍
Humidity
Operating
Damp Heat – Steady State (per IEC 68-2-3)
Damp Heat – Cyclic (per IEC 68-2-30)
5…95% Non-condensing
92% r.h., 40 C (104 F), 56 days
93% r.h., 25 C/40 C (77 F/104 F), 21 Cycles
Cooling Method Natural Convection
Vibration (per IEC 68-2-6) 2.5G operating, 5 G non-operating
Shock (per IEC 68-2-27) 30 G
Maximum Altitude 2000 m
Pollution Environment Pollution Degree 3
Terminal Marking EN 50012
Degree of Protection IP20
Control Module
Voltage
Relay 0
Current
Relay 1
Current
Relay 2
Current
Number of
Digital Inputs
Active
Operating Temperature
Range
Open Application
120/240V AC
1.0 A 1.0 A 1.0 A 4 -20…+55 °C (-4…+131 °F)
5.0 A 1.0 A 1.0 A 4 -20…+50 °C (-4…+122 °F)
24V DC
0.2 A 0.2 A 0.2 A 4 -20…+55 °C (-4…+131 °F)
0.2 A 0.2 A 0.2 A 6 -20…+50 °C (-4…+122 °F)
5.0 A 1.0 A 1.0 A 6 -20…+30 °C (-4…+86 °F)
Enclosed
Application
120/240V AC 5.0 A 5.0 A 5.0 A 4 -20…+40 °C (-4…+104 °F)
24V DC
0.2 A 0.2 A 0.2 A 4 -20…+40 °C (-4…+104 °F)
5.0 A 1.0 A 1.0 A 6 -20…+30 °C (-4…+86 °F)

Table of Contents

Other manuals for Allen-Bradley E300