154 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 4 System Operation and Configuration
• Non-Reversing Starter
• Reversing Starter
• Wye/Delta (Star/Delta) Starter
• Two-Speed Starter
• Monitor
The default Operating Mode (Parameter 195) for the E300 relay is Overload
(Network) in which the E300 relay operates like a traditional overload relay in
which one of the output relays is assigned as a Trip Relay or Control Relay. You
can use network commands to control any output relays that are assigned as
Normal output relays or Control Relays. For Control Module firmware v1.000
and v2.000, one output relay must be assigned as a Trip Relay. For Control
Module firmware v3.000 and higher, one output relay must be configured as a
Trip Relay or Control Relay. Invalid configuration of the output relays causes the
E300 relay to go into Invalid Configuration Mode and trip on a configuration
trip. Operating Modes on page 155
describes the functionality of the available
Operating Modes for the E300 relay and their associated configuration rules.