154 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 4 System Operation and Configuration
Non-Reversing Starter
Reversing Starter
Wye/Delta (Star/Delta) Starter
Two-Speed Starter
Monitor
The default Operating Mode (Parameter 195) for the E300 relay is Overload
(Network) in which the E300 relay operates like a traditional overload relay in
which one of the output relays is assigned as a Trip Relay or Control Relay. You
can use network commands to control any output relays that are assigned as
Normal output relays or Control Relays. For Control Module firmware v1.000
and v2.000, one output relay must be assigned as a Trip Relay. For Control
Module firmware v3.000 and higher, one output relay must be configured as a
Trip Relay or Control Relay. Invalid configuration of the output relays causes the
E300 relay to go into Invalid Configuration Mode and trip on a configuration
trip. Operating Modes on page 155
describes the functionality of the available
Operating Modes for the E300 relay and their associated configuration rules.

Table of Contents

Other manuals for Allen-Bradley E300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley E300 and is the answer not in the manual?

Allen-Bradley E300 Specifications

General IconGeneral
TypeElectronic Overload Relay
MountingDIN Rail or Panel Mount
Protection ClassIP20
Voltage Range24…690 V AC/DC
Communication OptionsEtherNet/IP, DeviceNet
ProtectionOverload, phase loss, ground fault
Operating Temperature-20°C to 60°C

Related product manuals