316 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 6 Protective Trip and Warning Functions
selected, the E300 Overload Relay can be manually reset after the % Thermal
Capacity Utilized is less than the OL Reset Level.
Table 231 - Overload Reset Mode (Parameter 173)
Table 232 - Overload Reset Level (Parameter 174)
Overload Reset Mode (Parameter 173)
Default Value 0 = Manual
Minimum Value 0 = Manual
Maximum Value 1 = Automatic
Parameter Type BOOL
Size (Bytes) 1
Scaling Factor 1
Units
Overload Reset Level (Parameter 174)
Default Value 75
Minimum Value 0
Maximum Value 100
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units %TCU