Rockwell Automation Publication 193-UM015E-EN-P - October 2015 341
Protective Trip and Warning Functions Chapter 6
Any relay outputs configured as a Trip Relay open
Any relay outputs configured as a Control Relay open
Any relay outputs configured as a Trip Alarm close
Any relay outputs configured as a Normal Relay are placed in their
Prote
ction Fault state (if so programmed)
L1 Under Current Trip Delay
L1 Under Current Trip Delay (Parameter 266) allows you to define the time
period an L1 Under Current condition must be present before a trip occurs. It is
adjustable from 0.1…25.0 seconds.
Table 263 - L1 Under Current Trip Delay (Parameter 266)
L1 Under Current Trip Level
L1 Under Current Trip Level (Parameter 267) allows you to define the current at
which the E300 relay trips on a L1 Under Current. It is user-adjustable from
10…100% of the FLA Setting (Parameter 171).
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
Output PT00 Protection Fault Action (Parameter 304)
Output PT00 Protection Fault Value (Parameter 305)
Output PT01 Protection Fault Action (Parameter 310)
Output PT01 Protection Fault Value (Parameter 311)
Output PT02 Protection Fault Action (Parameter 316)
Output PT02 Protection Fault Value (Parameter 317)
Output Digital Module 1 Protection Fault Action (Parameter 322)
Output Digital Module 1 Protection Fault Value (Parameter 323)
Output Digital Module 2 Protection Fault Action (Parameter 328)
Output Digital Module 2 Protection Fault Value (Parameter 329)
Output Digital Module 3 Protection Fault Action (Parameter 334)
Output Digital Module 3 Protection Fault Value (Parameter 335)
Output Digital Module 4 Protection Fault Action (Parameter 340)
Output Digital Module 4 Protection Fault Value (Parameter 342)
Default Value 1.0
Minimum Value 0.1
Maximum Value 25.0
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 10
Units Seconds