346 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 6 Protective Trip and Warning Functions
Table 268 - L2 Under Current Warning Level (Parameter 271)
L3 Under Current Trip
The E300 relay trips with a L3 Under Current indication if:
No trip currently exists
L3 Under Current Trip is enabled
Current is present
Under Current Inhibit Timer has expired
Percent FLA (Parameter 49) is less than the L3 Under Current Trip Level
f
or
a time period greater than the L3 Under Current Trip Delay.
If the E300 relay trips on a L3 Under Current, the:
TRIP/WARN LED status indicator flashes a red 10-short blink pattern
Bit 9 in Current Trip Status (Parameter 4) sets to 1
Bit 0 in Device Status 0 (Parameter 20) sets to 1
Any relay outputs configured as a Trip Relay open
Any relay outputs configured as a Control Relay open
Any relay outputs configured as a Trip Alarm close
Any relay outputs configured as a Normal Relay are placed in their
P
rote
ction Fault state (if so programmed)
Default Value 40
Minimum Value 10
Maximum Value 100
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units %FLA
IMPORTANT
The L2 Under Current Warning function does not include a time delay feature.
Once the Under Current Inhibit Timer has expired, the L2 Under Current
Warning indication is instantaneous.