354 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 6 Protective Trip and Warning Functions
Table 277 - L2 Over Current Trip Level (Parameter 280).
L2 Over Current Warning
The E300 relay indicates an L2 Over Current warning if:
No warning currently exists
2 Over Current Warning is enabled
Current is present
The Over Current Inhibit Timer has expired
2 Percent FLA (Parameter 48) is greater than the L2 Over Current
War n
in g L e vel
When the L2 Over Current Warning conditions are satisfied, the:
TRIP/WARN LED flashes a yellow 12-short blink pattern
Bit 11 in Current Warning Status (Parameter 10) sets to 1
Bit 1 in Device Status 0 (Parameter 20) sets to 1
Any relay outputs configured as a Warning Alarm closes
L2 Over Current Warning Level
L2 Over Current Warning Level (Parameter 281) allows you to define the current
at which the E300 relay indicates a L2 Over Current warning. It is user-adjustable
from 10…100% for the FLA Setting (Parameter 171).
Table 278 - L2 Over Current Warning Level (Parameter 281)
Default Value 100
Minimum Value 10
Maximum Value 100
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units %FLA
IMPORTANT
The Over Current Inhibit Timer starts after the maximum phase of load current
transitions from 0 A to 30% of the minimum FLA setting of the device. The
E300 relay does not begin monitoring for an overcurrent condition until the
Over Current Inhibit Time expires.
Default Value 90
Minimum Value 10
Maximum Value 100
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units %FLA