400 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 6 Protective Trip and Warning Functions
Under kVAR Generated Trip
The E300 relay trips with an Under kVAR Generated indication if:
No trip currently exists
Under kVAR Generated Trip is enabled
Current is present
Voltage is present
Under kVAR Generated Inhibit Time has expired
The total reactive power (kVAR) gen
era
ted is less than the Under
kVAR Generated Trip Level for a time period greater than the Under
kVA
R Generated Trip Delay.
If the E300 relay trips on an under reactive power (kVAR) generated, the:
TRIP/WARN LED status indicator flashes a red 2-long / 5-short blink
patter
n
B
it 4 in Power Trip Status (Parameter 6) sets to 1
Bit 0 in Device Status 0 (Parameter 20) sets to 1
Any relay outputs configured as a Trip Relay open
Any relay outputs configured as a Control Relay open
Any relay outputs configured as a Trip Alarm close
Any relay outputs configured as a Normal Relay are placed in their
Prote
ction Fault state (if so programmed)
IMPORTANT
The Over kVAR Consumed Warning function does not include a time delay
feature. Once the Over kVAR Consumed Inhibit Time has expired, the Over kVAR
Consumed Warning indication is instantaneous.